| 2023-05-24 11:42:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF A MODULE UNIT WITH A |
| | PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER, |
| | THERE IS NO INDICATION OF A FIRE SPRINKLER PROTECTION, |
| | |
| | PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES. |
| | |
| | 14.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | |
| | 14.3.5.1 EDUCATIONAL OCCUPANCY BUILDINGS SHALL BE |
| | PROTECTED THROUGHOUT |
| | BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE |
| | WITH SECTION 9.7 EXCEPT AS OTHERWISE PERMITTED BY |
| | 14.3.5.2. |
| | 14.3.5.2 THE REQUIREMENT OF 14.3.5.1 SHALL NOT APPLY TO |
| | ANY OF THE |
| | FOLLOWING: |
| | (1) NON-RELOCATABLE BUILDINGS HAVING AN AREA NOT |
| | EXCEEDING 1000 FT2 |
| | (93 M2 |
| | ) |
| | (2) NON-RELOCATABLE BUILDINGS CONTAINING A SINGLE |
| | CLASSROOM |
| | (3) RELOCATABLE BUILDINGS COMPLYING WITH ALL OF THE |
| | FOLLOWING: |
| | (A) BUILDING AREA DOES NOT EXCEED 1000 FT2 |
| | (93 M2 |
| | ) |
| | (B) BUILDING CONTAINS A SINGLE CLASSROOM |
| | (C) BUILDING IS LOCATED NOT LESS THAN 30 FT (9.1 M) |
| | FROM ANOTHER |
| | BUILDING |
| | 14.3.5.3 EVERY PORTION OF EDUCATIONAL BUILDINGS BELOW |
| | THE LEVEL OF EXIT |
| | DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP |
| | DRAWINGS. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION OF A MODULE UNIT WITH A |
| | PROPOSED USE AS AN EDUCATIONAL OCCUPANCY, HOWEVER, |
| | THERE IS NO INDICATION OF A FIRE ALARM PROTECTION. |
| | |
| | PER NFPA 101, CH 14, NEW EDUCATIONAL OCCUPANCIES. |
| | |
| | 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 14.3.4.1 GENERAL. |
| | 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| | 14.3.4.1.2 THE REQUIREMENT OF 14.3.4.1.1 SHALL NOT |
| | APPLY TO BUILDINGS |
| | MEETING ALL OF THE FOLLOWING CRITERIA: |
| | (1) BUILDINGS HAVING AN AREA NOT EXCEEDING 1000 FT2 |
| | (93 M2 |
| | ) |
| | (2) BUILDINGS CONTAINING A SINGLE CLASSROOM |
| | (3) BUILDINGS LOCATED NOT LESS THAN 30 FT (9.1 M) FROM |
| | ANOTHER |
| | BUILDING |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT TO PROVIDE A SEPARATE PERMIT & SHOP |
| | DRAWINGS. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |