| Plan Review Notes For Permit 23051022 |
| Permit Number |
23051022 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2023-07-19 16:17:17 | RESIDENTIAL (R3) RE-ROOF FIFTH BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23051022 | | | 333 MURRAY RD | | | | | | PREVIOUS COMMENT FOR FLAT ROOF: | | | 2- NEW FLAT ROOF NOA 22-0706.08 WAS SUBMITTED. NEED TO | | | CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE | | | INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | | | | PREVIOUS COMMENT: | | | 4- TU PLUS FLORIDA PRODUCT APPROVAL FL-5259-R38 | | | SUBMITTED SAYS "PENDING FBC APPROVAL". NEED TO PROVIDE | | | APPROVED PRODUCT APPROVAL. | | | F.A.C. 61G20.3.001. | | | | | | RESPONSE: | | | NEW FLORIDA PRODUCT APPROVAL FL5259-R39 SUBMITTED | | | DOESN'T IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED. CLEARLY MARK WHICH APPROVED ASSEMBLY FROM | | | SECTION 6.1 OF PRODUCT APPROVAL SUBMITTED. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|