| Notes |
| Date |
Text |
| 2023-06-22 10:07:00 | PLAN DENIED | | | 1) PROVIDE OUTDOOR AIR CALCULATIONS TO MEET | | | TABLE 403.1.1 FBC (M) 2020 | | | 2) NOT SHOWING DUCTWORK ON UNITS 2, 3, OR 4 | | | PLEASE EXPLAIN WHY. SECTION 107 FBC. | | | 3) PLEASE LABEL ALL ROOMS FOR THIS REVIEW. | | | 107 FBC | | | 4) REFER TO SECTION C403.2.1 CALCULATIONS | | | OF HEATING AND COOLING LOADS. FBC (ENERGY) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|