Plan Review Notes
Plan Review Notes For Permit 23050954
Permit Number 23050954
Review Stop Z
Sequence Number 1
Notes
Date Text
2023-06-15 11:55:47FAILED
  
 PER ZONING AND LAND DEVELOPMENT REGULATION SECTION
 94-72(A)(1)(D), FLAGLER DRIVE IS CONSIDERED THE FRONT
 OF THE PROPERTY, THEREFORE, THE PROPOSED LOGGIA IS
 ENCROACHING INTO THE FRONT SETBACK.
 THE NORTH PROPERTY LINE IS THE ???CORNER;??? THE SOUTH
 IS THE ???SIDE;??? EAST IS THE FRONT; AND WEST IS THE
 ???REAR.??? UPDATE PLANS AND SURVEY TO REFLECT THE
 APPROPRIATE SETBACKS FOR THE PRINCIPAL STRUCTURE. PER
 ZLDR SECTION 94-72(A)(2) THE MINIMUM SETBACKS FOR THE
 PRINCIPAL BUILDING ARE AS FOLLOWS - FRONT: 25 FEET;
 CORNER: 12.5 FEET; REAR: 15 FEET OR TEN PERCENT OF LOT
 DEPTH, WHICHEVER IS LESS; SIDE: FIVE FEET MINIMUM, 15
 FEET TOTAL.
  
 POOL/MECHANICAL EQUIPMENT CANNOT ENCROACH MORE THAN 4FT
 INTO REQUIRED SETBACK.
  
 SEPARATE PERMIT REQUIRED FOR:
 FENCE/WALL, DRIVEWAY, POOL, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, LANDSCAPE,
 ACCESSORY STRUCTURE, ETC.
  