| Date |
Text |
| 2023-05-25 15:40:55 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | PROVISO ON PLAN PAGE SP1.01: A SEPERATE PERMIT IS |
| | REQUIRED FOR THE GENERATOR. CT |
| | |
| | PROVISO ON PLAN PAGE E1.01: A SEPERATE PERMIT IS |
| | REQUIRED FOR HURRICANE SCREENS. CT |
| | |
| | NOTICE: |
| | SUB-PERMITS REQUIRED FOR M/E/P/GAS |
| | 105.1 REQUIRED. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | |
| | 1. APPROVAL OF THE CONSTRUCTION DRAWING ELEVATION |
| | CERETIFICATE IS REQUIRED PRIOR TO APPORVAL OF THE |
| | BUILDING REVIEW. |
| | SEE COMMENTS UNDER THE NFIP REVIEW. |
| | |
| | 2. PLAN PAGE A1.10 STATES 6 SMART VENTS, MODEL 1540-520 |
| | WILL BE INSTALLED WITH 2 VENTS PER LOCATION. PROVIDE |
| | LOCATION AND ORIENTATION OF VENTS ON THE ARCHITECTURAL |
| | ELEVATION PLANS. |
| | IF THE ORIENTATION IS VERTICAL, CONSIDER USING SMART |
| | VENT MODEL 1540-521 - STACKABLE. (400SF/VENT) |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 3. PROVIDE THE MANUFACTURERS SPECIFICATIONS FOR THE |
| | ELEVATOR. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |