Plan Review Notes
Plan Review Notes For Permit 23050946
Permit Number 23050946
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-30 15:47:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF INSTALL NEW TILE
 THROUGHOUT THE UNIT, HOWEVER, THERE IS NO TILE TYPE
 INDICATED NOR, IF APPLICABLE, A MANUFACTURER'S
 SPECIFICATION SHEET NOR A PRODUCT NAME.
  
 THERE IS ALSO NO INDICATION OF A SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT NOR THE PRODUCT NAME.
  
 TILEL FLOORING CAN HAVE DIFFERENT MEANINGS OF THE
 PTODUCT TYPE AND IS MANUFACTURED AROUND THE WORLD BUT
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE NAME AND, IF APPLICABLE, THE PRODUCT SPEC SHEETS
 INDICATING THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS INDICATION OF BATHROOM WORK THAT MAY
 INVOLVE A FIRE RATED TENANT/CORRIDOR SEPARATION WALL.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS ARE
 MAINTAINED & REPAIRED IF DAMAGED.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON
 THE PLAN.
  
  
  
 3) THERE IS INDICATION OF PAINTING THE UNIT WITH 2
 COATES OF PAINT WORK. THERE ARE FIRE SPRINKLER HEADS
 AND FIRE ALARM DEVICES AND SMOKE ALARMS IN THE UNIT.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE
 CORRECTED/REPAIRED UNDER SEPARATE PERMIT AND SHOP
 DRAWING BY FS/FA CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON
 THE PLAN.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC