| 2023-05-26 13:44:07 | FBC-2020 RES. PLUMBING | | | PERMIT- 23050903 | | | 5/26/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P104: PLEASE REMOVE THE GREASE INTERCEPTOR | | | FROM THE DRAWING. THIS PROPOSED PROJECT IS AN ADDITION | | | TO A SINGLE-FAMILY RESIDENTIAL HOME AND GREASE | | | INTERCEPTORS ARE NOT REQUIRED PER SEC. R101.2 FBC RES. | | | CODE & SEC. 90-125(7) WPB CODE OF ORDINANCES. IF THE | | | INTENTION IS TO CHANGE THE OCCUPANCY OF THE HOME AT A | | | LATER DATE AND INSTALL A GREASE INTERCEPTOR, THEN BOTH | | | THE CHANGE OF OCCUPANCY AND THE GREASE INTERCEPTOR | | | SHALL BE DONE UNDER SEPARATE PERMITS AND COMPLETE PLANS | | | AND SPECIFICATIONS SHALL BE PROVIDED FOR DEVELOPMENT | | | SERVICE DEPARTMENT REVIEW. PLEASE NOTE THE CURRENT PLAN | | | SHOWS THE SANITARY SEWER LINE FROM THE DOMESTIC | | | HOUSEHOLD FIXTURES DRAINING INTO THE GREASE INTERCEPTOR | | | WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|