| 2023-06-12 08:07:57 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23050901 |
| | 6/9/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED C0MMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW FAILED. |
| | |
| | A) THE NEW FIXTURE CALCULATIONS ON SHEET A-101 DO NOT |
| | INCLUDE THE BUSINESS OCCUPANCY REQUIREMENTS. |
| | |
| | B) BASED ON TABLE 403.1 A TOTAL OF (4) HI-LO DRINKING |
| | FOUNTAINS ARE REQUIRED. THE PLANS SHOW ONLY ONE HI-LO |
| | ON THE SECOND FLOOR PLEASE REFER TO SEC. 410.3 FBC P |
| | AND SEC. 211.2 FBC ACC. EACH OF THESE CODE SECTIONS |
| | REQUIRE THE HI-LO TYPE OF DRINKING FOUNTAIN. THE SINGLE |
| | FOUINTAIN WITH BOTTLE FILLER DOES NOT MEET COMPLIANCE |
| | WITH THE EXCEPTIONS LISTED UNDER THE SECTIONS. |
| | |
| | 2) COMMENT #2 FROM THE 1ST REVIEW FAILED. SHEETS P-001, |
| | P-202, P-204, & P-302: A HOSE BIB IS SHOWN IN THE 2ND |
| | FLOOR GIRLS RESTROOM HOWEVER HOSE BIBS ARE NOT SHOWN IN |
| | THE OTHER GROUP RESTROOMS. |
| | |
| | 3) COMMENT #4 FROM THE 1ST REVIEW FAILED. SHEETS P-001, |
| | P-202, P-204, & P-302: THE REQUIRED ASSE 1071 MIXING |
| | VALVE FOR THE EMERGENCY SHOWER AND EYE WASH STATIONS |
| | WAS NOT PROVIDED. |
| | |
| | 7) COMMENT #7 FROM THE 1ST REVIEW FAILED. SHEET A-212: |
| | THE DIMENSIONS OF THE CLEAR FLOOR SPACES WERE NOT |
| | PROVIDED. THE DIMENSIONS OF THE AMBULATORY COMPARTMENTS |
| | WERE NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |