| Plan Review Notes For Permit 23050901 |
| Permit Number |
23050901 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-12 11:32:23 | ELECTRIC REVIEW FAILED | | | | | | 1) ONE LINE RISER DIAGRAM ON SHEET E-401 DOES NOT | | | DETAIL PANEL 2NH. PLEASE CORRECT AS APPLICABLE. NEC | | | 215.5 | | | | | | 2 )PLEASE PROVIDE A NOTE ON SHEET E-101 THAT CAMPUS | | | MAIN ELECTRIC ROOM IS TO COMPLY WITH ALL APPLICABLE | | | REQUIREMENTS IN ACCORDANCE WITH NEC 110.26 "SPACES | | | ABOUT ELECTRICAL EQUIPMENT" WITH SPECIAL ATTENTION TO | | | LARGE EQUIPMENT AND EGRESS REQUIREMENTS | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|