| 2023-05-24 09:48:22 | ELECTRIC REVIEW FAILED |
| | |
| | PLEASE PROVIDE A NARRATIVE RESPONSE IN ADDITION TO ANY |
| | PLAN CHANGES TO EACH OF THE FOLLOWING COMMENTS: |
| | |
| | 1) ELECTRICAL WORK SCOPE IS NOT CLEAR. PLEASE PROVIDE A |
| | NARRATIVE AS WELL AS PLANS INDICATING PROPOSED AND |
| | EXISTING WORK, INCLUDING ALL TYPE AND LOCATIONS WHERE |
| | WORK IS TO BE PERFORMED. I.E. NEW SWITCHGEAR AND PANEL |
| | BOARDS, DUCT BANKS. FBC 107.2 NEC 215.5 |
| | |
| | 2) SITE PLAN INDICATES NO WORK CAMPUS MAIN ELECTRIC |
| | ROOM. HOWEVER, IT APPEARS A NEW MAIN SWITCH BOARD IS TO |
| | BE INSTALLED IN THIS BUILDING. PLEASE CORRECT OR |
| | PROVIDE ADDITIONAL CLARITY ON EQUIPMENT LOCATIONS. IN |
| | ADDITION, IT APPEARS THIS CAMPUS MAIN ELECTRIC ROOM IS |
| | LOCATED IN A MAINTENANCE BUILDING, HOWEVER THERE IS NO |
| | LOCATION GIVEN FOR THIS BUILDING ON SITE PLAN. LOCATION |
| | DESIGNATIONS IN MANY AREAS ARE NOT CLEAR. FBC 107.2 |
| | |
| | 3) PLEASE USE THE PROPER IDENTIFYING NAMES ON ALL PLANS |
| | FOR ELECTRICAL EQUIPMENT. I.E. NOTE 4 ON SITE PLAN, |
| | MAIN ELECTRIC PANEL SHOULD BE CORRECTLY IDENTIFIED WITH |
| | PANEL DESIGNATION. FBC 107.2 |
| | |
| | 4) PROVIDE A MAIN ELECTRICAL ROOM FLOOR PLAN AS |
| | REFERENCED BY NOTE 1 ON SHEET E-401. FBC 107.2 |
| | |
| | 5) PLEASE INDICATE PURPOSE OF REFERRING TO SWBD AS MAIN |
| | 1 OF 1. PLEASE PROVIDE CLARITY OF THE PURPOSE OF THIS |
| | DESIGNATION. FBC 107.2 |
| | |
| | 6) PLEASE PROVIDE ADDITIONAL CLARITY OF RISER DIAGRAM |
| | FOR MULTIPLE FEEDS TO MODULAR SWITCHBOARD. NEC 215.5 |
| | |
| | 7) PLEASE ADD A NOTE STATING SEPARATE PERMITS ARE |
| | REQUIRED FOR ALL LOW VOLTAGE SYSTEMS SUCH AS BUT NOT |
| | LIMITED TO, FIRE ALARM, VOICE, DATA, SECURITY, ACCESS |
| | CONTROL ETC. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |