| 2023-05-30 06:06:56 | 2ND GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. NOT ADDRESSED - NEED A SITE PLAN SHOWING THE TANK'S |
| | LOCATION ON THE PROPERTY --- |
| | 2017 WPB AMEND 107.3.5.3 (13) - A SITE PLAN IS REQUIRED |
| | FOR THE LOCATION OF THE TANK, GAS LINE AND GENERATOR. |
| | |
| | 2. NOT ADDRESSED - AN ENGINEER'S STAMP ON A DIGITAL |
| | SUBMITTAL IS NOT ACCEPTED. IT MUST BE AN ELECTRONIC |
| | SEAL ON THE FILE ITSELF - |
| | 2017 WPB AMEND 105.3.1.2 - THE REQUIRED TIE DOWN SPECS |
| | SUBMITTED HAVE AN ENGINEERS STAMP/SEAL. THE DATE OF THE |
| | SEAL IS FROM 2017 AND WOULD NEED TO BE CURRENT IF THE |
| | ENGINEER'S SEAL IS USED. THE SAME GOES FOR THE TANK |
| | SPECS. IF AN ENGINEER IS REQUIRED AND YOU CHOOSE TO USE |
| | THEIR SIGNATURE, IT MUST MEET THE REQUIREMENTS SET IN |
| | THE STATUTE. ALL ELECTRONIC SUBMISSIONS PREPARED BY AN |
| | ENGINEER MUST COMPLY WITH 61G15-23.001 AND BE EITHER |
| | DIGITALLY SIGNED AND SEALED -OR- ELECTRONICALLY SIGNED |
| | AND SEALED, IN ACCORDANCE WITH 61G15-23.004 AND |
| | 61G15-23.005 F.A.C. RESPECTIVELY. |
| | |
| | 3. NOT ADDRESSED - AS SITE PLAN SHOWING ITS LOCATION |
| | AND SEPARATION FROM STRUCTURE OPENINGS IS REQUIRED -- |
| | 2020 FRC R303.5.1 - RESIDENTIAL GAS GENERATORS MUST BE |
| | 10 FEET FROM OPENINGS. |
| | |
| | 4. NOT ADDRESSED - A SITE PLAN SHOWING ITS LOCATION IS |
| | REQUIRED - |
| | 2020 FRC G2412.2 (401.2)/2018 NFPA 6.4.1.1 - AN |
| | UNDERGROUND TANK SHALL BE 10 FEET FROM AN IMPORTANT |
| | BUILDING OR LINE OF ADJOINING PROPERTY THAT CAN BE |
| | BUILT UPON PER TABLE 6.4.1.1, TABLE 6.5.1.2, 6.4.1.2 |
| | THROUGH 6.4.1.3, 6.4.3, 6.4.4.1 THROUGH 6.4.4.4, AND |
| | 6.5.3.6 THROUGH 6.5.3.11. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |
| | |