| 2023-06-12 14:57:13 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23050859 |
| | 6/12/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1.1: DRINKING FOUNTAINS (HI & LO) AND A |
| | SERVICE SINK ARE REQUIRED FOR M OCCUPANCIES- TABLE |
| | 403.1 AND SEC. 410.3 FBC P. SHOW THE FIXTURE LOCATIONS |
| | AND REVISE THE PLUMBING PIPING DRAWINGS ACCORDINGLY- |
| | SECS. 107.2.1 & 107.3.5.1.3 WPB. |
| | |
| | 2) P-1.1: AN ASSE 1070 MIXING VALVE FOR TEMPERED WATER |
| | IS REQUIRED FOR THE H AND C WATER LINES TO THE |
| | LAVATORY- SEC. 419.5 & 607.1.2 FBC P. |
| | |
| | 3) A6.0: FBC ACCESSIBILITY CORRECTIONS: |
| | A) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE |
| | FOR THE LAVATORY- 603.2.3. |
| | B) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| | FOR THE WATER CLOSET- 604.3.1 & 604.3.2. |
| | C) SHOW THE 19-INCH MAXIMUM HEIGHT OF THE WATER CLOSET |
| | SEAT FROM THE FINISHED FLOOR- 604.4. |
| | |
| | 4) P-1.1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| | WALK-IN FRIDGE- SEC. 314.2- 314.2.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |