Plan Review Notes
Plan Review Notes For Permit 23050829
Permit Number 23050829
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-08 12:55:44 
 THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
 THERE ARE INDICATIONS OF INSTALLATION OF NEW FLOORING
 BUT NO SPECIFICATIONS SHEETS THAT INDICATE MEETING THE
 REQUIREMENTS PER NFPA'
  
 PER NFPA 101, CH 10
  
  
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 2) THERE ARE INDICATIONS OF WALL AND VANITY REPLACEMENT
 AND PAINTING.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]
  
  