| Plan Review Notes For Permit 23050828 |
| Permit Number |
23050828 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-14 16:58:16 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-23050828 | | | 6/14/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-102: THE FLOOR SINK TRAP DISTANCE TO THE | | | SINK VENT APPEARS TO BE EXCEEDING THE MAXIMUM 8 FT. | | | ALLOWABLE PER TABLE 909.1 FBC P. | | | | | | 2) P-102: PROVIDE A UL TESTED AND APPROVED FIRESTOPPING | | | DETAIL FOR SEALING THE ANNUAL SPACE AROUND THE FLOOR | | | SINK AND DRAIN PIPE SLAB PENETRATION- SEC. 315.1 FBC P | | | & SEC. 714.4.1.2 FBC B. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|