2023-06-14 16:58:161ST REVIEW FBC-2020 PLUMBING
 PERMIT-23050828
 6/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-102: THE FLOOR SINK TRAP DISTANCE TO THE
 SINK VENT APPEARS TO BE EXCEEDING THE MAXIMUM 8 FT.
 ALLOWABLE PER TABLE 909.1 FBC P.
  
 2) P-102: PROVIDE A UL TESTED AND APPROVED FIRESTOPPING
 DETAIL FOR SEALING THE ANNUAL SPACE AROUND THE FLOOR
 SINK AND DRAIN PIPE SLAB PENETRATION- SEC. 315.1 FBC P
 & SEC. 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  