2023-06-28 10:32:49PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 R301.2.1.2 PROTECTION OF OPENINGS. EXTERIOR GLAZED
 OPENINGS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL BE PROTECTED FROM WINDBORNE DEBRIS.
  
 SUBMIT AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE
 STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND
 PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE
 DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE
 FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER
 FROM THE INSTALLATION DRAWINGS. PLEASE CONTACT ME IF
 YOU WOULD LIKE ME TO SEND YOU A CITY OF WPB BLANK
 SCHEDULE.