2023-05-25 17:32:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050638
 5/25/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P300 DETAIL 8: THE EXPANSION TANKS HALL BE
 LOCATED AT A POINT ON THE COLD WATER FEED THAT IS
 DOWNSTREAM OF THE CHECK VALVE- SEC. 607.3 FBC P.
  
 2) P200, P300, P400: THE THERMOSTAT CONTROL ON THE
 WATER HEATER CANNOT BE THE LIMITING DEVICE FOR HOT
 WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING
 DEVICE FOR THE PURPOSE OF HOT WATER DELIVERY. THIS
 WOULD BE IN ADDITION TO THE REQUIREMENTS FOR TEMPERED
 WATER FOR PUBLIC HAND-WASHING 607.1.2/419.5 FBC P.
 TYPICALLY A MASTER THERMOSTATIC MIXING VALVE COMPLYING
 WITH ASSE 1017 WOULD MEET COMPLIANCE. PLEASE REVISE THE
 PLAN ACCORDINGLY AND SHOW THE REQUIRED PIPING
 CONNECTIONS PER SEC. 607.2.2.
  
 3) A625 DETAIL C: THE CENTERLINE OF THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND
 9-INCHES MAXIMUM FROM THE FRONTS OF THE WATER CLOSETS-
 SEC. AND FIGURE 604.7. THE DETAIL DOES NOT SHOW THE
 8-INCH MEASUREMENT TO THE CENTER OF THE DISPENSER-
 PLEASE CORRECT.
  
 4) A113: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND THE
 KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN- SEC. 602.2 FBC ACC.
  
 A) PROVIDE AN ELEVATION DETAIL SHOWING THE HI AND LO
 SPOUT HEIGHTS- SECS. 602.4 & 602.7.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  