| 2023-05-25 17:32:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23050638 |
| | 5/25/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P300 DETAIL 8: THE EXPANSION TANKS HALL BE |
| | LOCATED AT A POINT ON THE COLD WATER FEED THAT IS |
| | DOWNSTREAM OF THE CHECK VALVE- SEC. 607.3 FBC P. |
| | |
| | 2) P200, P300, P400: THE THERMOSTAT CONTROL ON THE |
| | WATER HEATER CANNOT BE THE LIMITING DEVICE FOR HOT |
| | WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING |
| | DEVICE FOR THE PURPOSE OF HOT WATER DELIVERY. THIS |
| | WOULD BE IN ADDITION TO THE REQUIREMENTS FOR TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING 607.1.2/419.5 FBC P. |
| | TYPICALLY A MASTER THERMOSTATIC MIXING VALVE COMPLYING |
| | WITH ASSE 1017 WOULD MEET COMPLIANCE. PLEASE REVISE THE |
| | PLAN ACCORDINGLY AND SHOW THE REQUIRED PIPING |
| | CONNECTIONS PER SEC. 607.2.2. |
| | |
| | 3) A625 DETAIL C: THE CENTERLINE OF THE TOILET PAPER |
| | DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND |
| | 9-INCHES MAXIMUM FROM THE FRONTS OF THE WATER CLOSETS- |
| | SEC. AND FIGURE 604.7. THE DETAIL DOES NOT SHOW THE |
| | 8-INCH MEASUREMENT TO THE CENTER OF THE DISPENSER- |
| | PLEASE CORRECT. |
| | |
| | 4) A113: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND THE |
| | KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR ACCESSIBLE |
| | DRINKING FOUNTAIN- SEC. 602.2 FBC ACC. |
| | |
| | A) PROVIDE AN ELEVATION DETAIL SHOWING THE HI AND LO |
| | SPOUT HEIGHTS- SECS. 602.4 & 602.7. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |