| Date |
Text |
| 2023-06-06 16:30:34 | BUILD OUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A FIRE WALL HOURLY RATING SCHEDULE - |
| | SHOWING THE TENANT SEPARATION WALL AND THE EXIT PATHWAY |
| | WALL HOURLY RATING FOR THE ADJACENT TENNANTS - FBC WPB |
| | 107.3.5 |
| | |
| | 2) DRAWING A 401 - PLEASE SHOW THE EXTERIOR WALL |
| | SHEATHING ATTACHMENTS - FBC 1609 |
| | |
| | 3) DRAWING A 401 - PLEASE SHOW THE EXTERIOR WALL WATER |
| | RESISTIVE BARRIER - FBC 1404.2 WATER-RESISTIVE BARRIER. |
| | NOT FEWER THAN ONE LAYER OF NO.15 ASPHALT FELT, |
| | COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR OTHER |
| | APPROVED MATERIALS, SHALL BE ATTACHED TO THE STUDS OR |
| | SHEATHING, WITH FLASHING AS DESCRIBED IN SECTION |
| | 1405.4, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS |
| | WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR WALL |
| | VENEER. |
| | |
| | 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS AND DOORS - |
| | ALL PRODUCT APROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE DESIGNER OF RECORD OR BE LISTED ON THE |
| | DRAWINGS BY THE PRODUCT APPROVAL NUMBER. FBC 107.3.4 |
| | |
| | 5) ACCESSIBLE RESTROOM = PLEASE SHOW THE DIMENSIONS FOR |
| | THE TOILET REAR GRAB BAR FROM THE CENTER OF THE TOILET |
| | NOT 6 INCHES FROM THE WALL - FBC A 604.5.2REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 6) ACCESSIBLE RESTROOM = THE VERTICAL TOILET GRAB BAR |
| | IS NOT A REQUIREMENT OF THE FBC - PLEASE SHOW THE 12 |
| | INCH CLEARANCE ABOVE THE HORIZONTAL GRAB BAR PER FBC A |
| | 609.3 THE SPACE BETWEEN THE GRAB BAR AND PROJECTING |
| | OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) MINIMUM. |