Plan Review Notes
Plan Review Notes For Permit 23050632
Permit Number 23050632
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-14 16:35:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050632
 6/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLUMBING PLAN: INDICATE THE TYPE AND SIZE OF WATER
 SERVICE LINE, POINT OF CONNECTION TO THE EXISTING
 BUILDING SERVICE, UNDERGROUND OR ABOVEGROUND
 INSTALLATION, AND LOCATIONS OF SHUTOFF VALVES AND
 REQUIRED BACKFLOW PREVENTER- SECS. 602.1, 603.2, &
 608.3 FBC P. INDICATE THE TYPE AND SIZE OF BACKFLOW
 PREVENTER TO BE INSTALLED- SEC. 608.3 FBC P.
  
 2) PLUMBING PLAN: SHOW THE TYPE AND SIZE OF TEMPORARY
 SEWER LINE AND CLEANOUT LOCATIONS- SECS. 701.2, 701.3 &
 708.1.2 FBC P.
  
 3) PLUMBING RISER: THE INTERIOR PIPING, FIXTURES AND
 WATER HEATER SHOWN IN THE RISERS APPEAR TO BE FACTORY
 INSTALLED IN THE MANUFACTURED BUILDING. PLEASE PLACE A
 NOTE ON THE PLAN TO CLARIFY- SEC. 107.2.1 WPB.
  
 4) THE CORRECTED PLUMBING PLAN AND RISER DRAWING SHALL
 BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 OR QUALIFIER WHO PREPARED THE DESIGN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  