| 2023-06-14 16:35:41 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23050632 |
| | 6/14/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLUMBING PLAN: INDICATE THE TYPE AND SIZE OF WATER |
| | SERVICE LINE, POINT OF CONNECTION TO THE EXISTING |
| | BUILDING SERVICE, UNDERGROUND OR ABOVEGROUND |
| | INSTALLATION, AND LOCATIONS OF SHUTOFF VALVES AND |
| | REQUIRED BACKFLOW PREVENTER- SECS. 602.1, 603.2, & |
| | 608.3 FBC P. INDICATE THE TYPE AND SIZE OF BACKFLOW |
| | PREVENTER TO BE INSTALLED- SEC. 608.3 FBC P. |
| | |
| | 2) PLUMBING PLAN: SHOW THE TYPE AND SIZE OF TEMPORARY |
| | SEWER LINE AND CLEANOUT LOCATIONS- SECS. 701.2, 701.3 & |
| | 708.1.2 FBC P. |
| | |
| | 3) PLUMBING RISER: THE INTERIOR PIPING, FIXTURES AND |
| | WATER HEATER SHOWN IN THE RISERS APPEAR TO BE FACTORY |
| | INSTALLED IN THE MANUFACTURED BUILDING. PLEASE PLACE A |
| | NOTE ON THE PLAN TO CLARIFY- SEC. 107.2.1 WPB. |
| | |
| | 4) THE CORRECTED PLUMBING PLAN AND RISER DRAWING SHALL |
| | BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR |
| | OR QUALIFIER WHO PREPARED THE DESIGN- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |