| Plan Review Notes For Permit 23050573 |
| Permit Number |
23050573 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-26 14:34:01 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. SIGN MUST BE CONTROLLED BY AN EXTERNALLY OPERABLE | | | SWITCH OR CIRCUIT BREAKER THAT OPENS ALL UNGROUNDED | | | CONDUCTORS. NEC 600.6 | | | NOTE: THE DISCONNECTING MEANS MUST BE WITHIN SIGHT OF | | | THE SIGN. NEC 600.6(A)(1) | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN P. PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] |
|