2023-05-31 06:16:381ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3101.2.1 - THE WATER CLOSET IN THE POWDER
 BATH NEXT TO THE PANTRY IS NOT VENTED TO CODE. THE
 LAUNDRY TUB AND/OR WASHING MACHINE CANNOT ACT AS THE
 WET VENT AS THEY ARE NOT BATHROOM GROUP FIXTURES. ONLY
 BATHROOM GROUP FIXTURES CAN BE INCLUDED IN WET VENTS.
  
 2. CITY ORD. SEC. 90 - 126. - ON PAGE P1.1 - BETWEEN
 LIVING ROOM AND FAMILY ROOM NEAR FOYER, THERE IS A KEY
 NOTE "8" THAT INDICATES THERE IS A CONDENSATE THAT
 DISCHARGES INTO THE SANITARY. PLEASE FIX THE KEY NOTE.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  