| Plan Review Notes For Permit 23050553 |
| Permit Number |
23050553 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-31 06:16:38 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3101.2.1 - THE WATER CLOSET IN THE POWDER | | | BATH NEXT TO THE PANTRY IS NOT VENTED TO CODE. THE | | | LAUNDRY TUB AND/OR WASHING MACHINE CANNOT ACT AS THE | | | WET VENT AS THEY ARE NOT BATHROOM GROUP FIXTURES. ONLY | | | BATHROOM GROUP FIXTURES CAN BE INCLUDED IN WET VENTS. | | | | | | 2. CITY ORD. SEC. 90 - 126. - ON PAGE P1.1 - BETWEEN | | | LIVING ROOM AND FAMILY ROOM NEAR FOYER, THERE IS A KEY | | | NOTE "8" THAT INDICATES THERE IS A CONDENSATE THAT | | | DISCHARGES INTO THE SANITARY. PLEASE FIX THE KEY NOTE. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | | | | |
|