| 2023-06-27 15:31:49 | 1ST NFIP REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935 |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 |
| | FEMA DESK REFERENCE P 758 |
| | FBC R322 FLOOD-RESISTANT CONSTRUCTION |
| | |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE |
| | IS AE 7 WITH A BASE FLOOD ELEVATION (BFE) OF 7???0??? |
| | NAVD. |
| | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. |
| | 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. |
| | THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE |
| | 9???0??? NAVD. |
| | |
| | CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17 |
| | SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT |
| | CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE |
| | II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL |
| | AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH |
| | SHALL READ AS FOLLOWS: |
| | SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| | CODE, RESIDENTIAL. |
| | R322.2.1 ELEVATION REQUIREMENTS. |
| | 1.BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT |
| | DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST |
| | FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION |
| | PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER |
| | IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17). |
| | |
| | 2. LINE A1 - THE CORRECT ADDRESS FOR THE PROPERTY IS |
| | 6625 S FLAGLER DR. |
| | 3. LINE A9D) STATES FLOOD OPENINGS ARE NON-ENGINEERED. |
| | PLAN PAGE A-002 SHOWS (4) ENGINEERED SMART VENTS |
| | INSTALLED. PLEASE CLARIFY? |
| | 4. LINE A8B) & C) SHALL BE N/A PER EC INSTRUCTIONS. |
| | 5. LINE A9 - YOU MAY ENTER A VALUE OF 800 IN THIS |
| | SECTION PER FEMA TECHNICAL BULLITEN #1 SECTION 9.PG. 39 |
| | 6. LINE B8 SHOULD BE X-500 AND AE7. |
| | 7. LINE B9 SHOULD BE 7.0' NAVD. |
| | 8. LINE C2B) - TOP OF NEXT HIGHEST FLOOR SHOULD BE |
| | 22.33' PER PLAN PAGE A-005. |
| | 9. LINE C2E) SHALL BE A MINIMUM OF 9.0' NAVD. |
| | 10. SECTION D COMMENTS - |
| | 10A) REMOVE - VACANT LOT. |
| | 10B) REMOVE - CROWN OF ROAD. |
| | 10C) REMOVE - THIS IS A PROPOSED EC. |
| | 10D) ADD - MACHINERY SERVICING THE BUILDING IN SECTION |
| | C2E) ARE A/C CONDENSING UNITS AT WEST ELEVATION OF |
| | BUILDING. |
| | 10E) ADD - SMART VENT MODEL # _________ |
| | 10F) ADD - COVERAGE PER VENT IS __________ |
| | |
| | NOTICE: PROVIDE THE FOLLOWING (3) ELEVATION |
| | CERTIFICATES AS REQUIRED. |
| | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. |
| | |
| | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AT PLACEMENT OF 1ST FLOOR. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |