Plan Review Notes
Plan Review Notes For Permit 23050553
Permit Number 23050553
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2023-06-27 15:31:491ST NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE
 IS AE 7 WITH A BASE FLOOD ELEVATION (BFE) OF 7???0???
 NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9???0??? NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1.BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17).
  
 2. LINE A1 - THE CORRECT ADDRESS FOR THE PROPERTY IS
 6625 S FLAGLER DR.
 3. LINE A9D) STATES FLOOD OPENINGS ARE NON-ENGINEERED.
 PLAN PAGE A-002 SHOWS (4) ENGINEERED SMART VENTS
 INSTALLED. PLEASE CLARIFY?
 4. LINE A8B) & C) SHALL BE N/A PER EC INSTRUCTIONS.
 5. LINE A9 - YOU MAY ENTER A VALUE OF 800 IN THIS
 SECTION PER FEMA TECHNICAL BULLITEN #1 SECTION 9.PG. 39
 6. LINE B8 SHOULD BE X-500 AND AE7.
 7. LINE B9 SHOULD BE 7.0' NAVD.
 8. LINE C2B) - TOP OF NEXT HIGHEST FLOOR SHOULD BE
 22.33' PER PLAN PAGE A-005.
 9. LINE C2E) SHALL BE A MINIMUM OF 9.0' NAVD.
 10. SECTION D COMMENTS -
 10A) REMOVE - VACANT LOT.
 10B) REMOVE - CROWN OF ROAD.
 10C) REMOVE - THIS IS A PROPOSED EC.
 10D) ADD - MACHINERY SERVICING THE BUILDING IN SECTION
 C2E) ARE A/C CONDENSING UNITS AT WEST ELEVATION OF
 BUILDING.
 10E) ADD - SMART VENT MODEL # _________
 10F) ADD - COVERAGE PER VENT IS __________
  
 NOTICE: PROVIDE THE FOLLOWING (3) ELEVATION
 CERTIFICATES AS REQUIRED.
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  