| 2023-06-27 14:15:49 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935 |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | NOTICE: THE SURVEY SUBMITTED FOR REVIEW STATES THE |
| | PROPERTY IS LOCATED ON FLOOD ZONE X. PALM BEACH COUNTY |
| | GIS SHOWS THE PROPERTY IS LOCATED IN A SPECIAL FLOOD |
| | HAZARD AREA (SFHA) WITH TWO FLOOD ZONES, X-500 AND AE7 |
| | WITH A BASE FLOOD ELEVATION (BFE) OF 7.0' NAVD. |
| | |
| | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| | SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PLAN PAGE A-002 SHOWS 4 FLOOD VENTS INSTALLED ON ONE |
| | WALL. FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS |
| | PER FEMA TECH. BULLITEN #1. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 3. IDENTIFY TYPE OF SMART VENTS TO BE INSTALLED ON |
| | FLOOR PLAN A-002. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 4. IDENTIFY COVERAGE EACH VENT PROVIDES ON FLOOR PLAN |
| | A-002. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 5.PROVIDE ROOF DRAINAGE PLAN |
| | R903.4ROOF DRAINAGE. |
| | UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF |
| | DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE |
| | ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL |
| | BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| | THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. |
| | R903.4.1OVERFLOW DRAINS AND SCUPPERS. |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| | VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET |
| | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| | OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION |
| | AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES. |
| | |
| | 6. SUBMIT A CORRECTED CONSTRUCTION DRAWING ELEVATION |
| | CERTIFICATE FOR REVIEW. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |