2023-06-27 14:15:491ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: THE SURVEY SUBMITTED FOR REVIEW STATES THE
 PROPERTY IS LOCATED ON FLOOD ZONE X. PALM BEACH COUNTY
 GIS SHOWS THE PROPERTY IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA) WITH TWO FLOOD ZONES, X-500 AND AE7
 WITH A BASE FLOOD ELEVATION (BFE) OF 7.0' NAVD.
  
 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PLAN PAGE A-002 SHOWS 4 FLOOD VENTS INSTALLED ON ONE
 WALL. FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS
 PER FEMA TECH. BULLITEN #1.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 3. IDENTIFY TYPE OF SMART VENTS TO BE INSTALLED ON
 FLOOR PLAN A-002.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 4. IDENTIFY COVERAGE EACH VENT PROVIDES ON FLOOR PLAN
 A-002.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 5.PROVIDE ROOF DRAINAGE PLAN
 R903.4ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE ROOF SLOPE AND CONTRIBUTING ROOF AREA.
 R903.4.1OVERFLOW DRAINS AND SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION
 AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES.
  
 6. SUBMIT A CORRECTED CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  