| Plan Review Notes For Permit 23050525 |
| Permit Number |
23050525 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-12 09:10:18 | SHORING AND RESHORING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE ENGINEER OF RECORD HAS A STATEMENT ON THE COVER | | | SHEET THAT STATES "RESUBMIT" - DRAWINGS AND | | | CALCULATIONS NEED TO BE REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD WITHOUT NEEDING CORRECTIONS. | | | | | | 2) THE SHOP DRAWINGS DO NOT SHOW IN ADOBE READER AS | | | DIGITALLY SIGNED BY THE ENGINEER ( EDUARDO CANTO)- | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|