| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN |
| | REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING: |
| | INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5 AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR |
| | PRODUCT APPROVAL FL1654-R30 SYSTEM NO. W-209 DO NOT |
| | MEET THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF |
| | -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM |
| | THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS |
| | FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | AS PER RULE 61G20-3. |
| | 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |