Plan Review Notes
Plan Review Notes For Permit 23050345
Permit Number 23050345
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-20 10:58:101ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23050345
 6/20/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON SECS. G2412.3 & G2412.4 FBC RES. PLEASE
 PROVIDE A GAS RISER DRAWING WHICH INCLUDES THE
 FOLLOWING INFORMATION:
  
 A) DELIVERY PRESSURE AT THE METER.
 B) BTU LOAD OF THE POOL HEATER.
 C) SHOW THE PIPING RUN FROM THE METER TO THE POOL
 HEATER INCLUDING THE TYPE AND SIZE OF PIPE, LENGTH OF
 THE PIPE, AND THE LOCATIONS OF TEES AND/OR BRANCH PIPE
 CONNECTIONS TO THE MAIN SUPPLY.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 F) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  