Plan Review Notes
Plan Review Notes For Permit 23050327
Permit Number 23050327
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-30 14:55:11ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE PANEL SCHEDULES AND LOAD CALCULATIONS
 FOR EACH MAIN SERVICE PANEL DETAILING AMPACITY OF
 FEEDERS, 130 AMP, #1 CU CONDUCTORS, HAVE AN AMPACITY OF
 NOT LESS THAN THE MAXIMUM LOAD SERVED IN ACCORDANCE
 WITH NEC 230.42(A).
  
 PLEASE NOTE THAT NEC 310.15 (B)(7)(2) IS NOT APPLICABLE
 TO THIS DESIGN AS THE SERVICE ENTRANCE CONDUCTORS DO
 NOT SERVE THE ENTIRE LOAD ASSOCIATED WITH THE DWELLING.
  
 HOWEVER, IF THE LOAD CALCULATED FOR EACH SET OF SERVICE
 ENTRANCE CONDUCTORS IS LESS THEN THE DESIGNED AMPACITY
 OF THE #1 CU CONDUCTORS, 130 AMPS, THEN THE NEXT HIGHER
 STANDARD SIZED OVERCURRENT PROTECTION OF 150 AMPS, MAY
 BE USED IN ACCORDANCE WITH NEC 240.4(B)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER