| Plan Review Notes For Permit 23050323 |
| Permit Number |
23050323 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-07 09:43:16 | ADD ANCHORS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SHOW THE CODE USED FOR DESIGN 2017 FBC AND | | | ASCE 7-10 - SHOULD BE 2020 FBC AND ASCE 7-16 | | | | | | 2) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | I CHECK THE ELECTRONIC SIGNATURE BY OPENING THEM IN | | | ???ADOBE READER???. THE ???ADOBE READER??? STATES | | | WHETHER THEY ARE AN ORIGINAL ELECTRONICALLY SIGNED | | | DOCUMENT. WHEN ELECTRONICALLY SIGNED DRAWINGS ARE | | | PRINTED OUT, THEY LOSE THEIR ELECTRONIC SIGNATURE. | | | ELECTRONICALLY SIGNED DRAWINGS NEED TO BE MOVED AROUND | | | IN THE COMPUTER FROM PLACE TO PLACE. FROM THE | | | ARCHITECT???S OR ENGINEER???S COMPUTER TO YOUR COMPUTER | | | TO THE CITY???S ELECTRONIC PLAN REVIEW (PROJECTDOX). | | | MAYBE YOURS WERE PRINTED OUT AT SOME TIME? |
|