| 2023-05-31 14:25:02 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23050314 | | | 5/31/2023 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET G-01: GAS PERMIT #20090291 LISTED ON THE PLAN | | | WAS REJECTED IN PLAN REVIEW, WAS NOT ISSUED, EXPIRED, | | | AND WAS ULTIMATELY ABANDONED. IN ACCORDANCE WITH SEC. | | | 107.3.5.1.5 WPB COMPLETE GAS PLANS AND SPECIFICATIONS | | | ARE REQUIRED FOR THE NEW RESTAURANT INCLUDING THE | | | FOLLOWING ITEMS- | | | A) GAS PIPING LAYOUT PLAN AND RISER DRAWING. | | | B) GAS APPLIANCE SCHEDULE AND PRODUCT SPECIFICATION | | | SUBMITTALS (SUBMITTALS MAY BE DEFERRED AND ONSITE FOR | | | INSPECTION). | | | C) COMBUSTION AIR PLAN AND CALCULATIONS FOR GAS-FIRED | | | APPLIANCES. | | | D) GAS VENTING PLANS FOR ALL APPLIANCES REQUIRING | | | EXHAUST VENTILATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|