Plan Review Notes
Plan Review Notes For Permit 23050263
Permit Number 23050263
Review Stop E
Sequence Number 2
Notes
Date Text
2023-07-14 14:10:53FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONE DETAIL SHOWS CAMERAS ON POLES, IF THEY ARE TO BE
 INSTALLED PLEASE SHOW COMPLIANCE WITH 725.136
  
 725.136 SEPARATION FROM ELECTRIC LIGHT, POWER, CLASS 1,
 NON???POWER-LIMITED FIRE ALARM CIRCUIT CONDUCTORS, AND
 MEDIUM-POWER NETWORK-POWERED BROADBAND COMMUNICATIONS
 CABLES.
 (A) GENERAL.
  
 CABLES AND CONDUCTORS OF CLASS 2 AND CLASS 3 CIRCUITS
 SHALL NOT BE PLACED IN ANY CABLE, CABLE TRAY,
 COMPARTMENT, ENCLOSURE, MANHOLE, OUTLET BOX, DEVICE
 BOX, RACEWAY, OR SIMILAR FITTING WITH CONDUCTORS OF
 ELECTRIC LIGHT, POWER, CLASS 1, NON???POWER-LIMITED
 FIRE ALARM CIRCUITS, AND MEDIUM-POWER NETWORK-POWERED
 BROADBAND COMMUNICATIONS CIRCUITS UNLESS PERMITTED BY
 725.136(B) THROUGH (I).
  
 PLEASE PROVIDE A BREAKDOWN OF HOW MANYURES ARE BEING
 INSTALLED, OR RELOCATED.
  
 PERMIT VALUE TO INCLUDE ALL LABOR AND MATERIALS
 INVOLVED CUSTOMER OR CONTRACTOR SUPPLIED. PLEASE
 PROVIDE A COST BREAKDOWN OF WORK.
  
 FBC 109.2.1