Plan Review Notes For Permit 23050263
Permit Number 23050263
Review Stop Z
Sequence Number 1
Notes
Date Text
2023-06-15 18:03:57FAILED
  
 1) THE POLE DETAIL SHOWN ON SHEET C901.6(E-16.0)
 DIFFERS FROM THE POLE DETAIL SHOWN ON SHEETS C901.0 AND
 C901.1. ALL SHEETS MUST SHOW THE SAME CONDITIONS.
  
 A. THE POLE PLUS FIXTRUE HEIGHTS DIFFE BY APPROXIMATELY
 SIX (6) FEET.
 B. THE POLE DETAIL ON SHEET C901.6(E-16.0) SHOWS
 SPOTLIGHTS MOUNTED TO THE POLES. YOU MUST DESIGNATE
 WHICH POLES THESE ARE LOCATED ON AND REFLECT THE
 PHOTOMETRICS ACCORDINGLY. PLEASE NOTE THAT THEIR
 POSITIONING MAY NOT RESULT IN GLARE IN THE RIGHT-OF-WAY
 OR RESIDENTIAL PROPERTY.
  
 2) THE FOOTCANDLE VALUES ON THE PHOTOMETRIC PLANS ARE
 VERY DIFFICULT TO READ. PLEASE MAKE THEM MORE LEGIBLE.
  
 3) THE ZONING AND LAND DEVELOPMENT REGULATIONS SPECIFY
 THAT ANY SOURCE OF ILLUMINATION LOCATED WITHIN A
 COMMERCIAL PLANNED DEVELOPMENT DISTRICT(WHICH IS
 APPLIES TO BRANDSMART/BJS) SHALL NOT EXCEED ONE
 FOOTCANDLE AT OR BEYOND THE BOUNDARIES OF SUCH
 DEVELOPMENT. THE ONE FOOTCANDLE MAXIMUM IS EXCEEDED IN
 A NUMBER OF LOCATIONS. THIS MUST BE CORRECTED.
  