| Plan Review Notes For Permit 23050263 |
| Permit Number |
23050263 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-15 18:03:57 | FAILED | | | | | | 1) THE POLE DETAIL SHOWN ON SHEET C901.6(E-16.0) | | | DIFFERS FROM THE POLE DETAIL SHOWN ON SHEETS C901.0 AND | | | C901.1. ALL SHEETS MUST SHOW THE SAME CONDITIONS. | | | | | | A. THE POLE PLUS FIXTRUE HEIGHTS DIFFE BY APPROXIMATELY | | | SIX (6) FEET. | | | B. THE POLE DETAIL ON SHEET C901.6(E-16.0) SHOWS | | | SPOTLIGHTS MOUNTED TO THE POLES. YOU MUST DESIGNATE | | | WHICH POLES THESE ARE LOCATED ON AND REFLECT THE | | | PHOTOMETRICS ACCORDINGLY. PLEASE NOTE THAT THEIR | | | POSITIONING MAY NOT RESULT IN GLARE IN THE RIGHT-OF-WAY | | | OR RESIDENTIAL PROPERTY. | | | | | | 2) THE FOOTCANDLE VALUES ON THE PHOTOMETRIC PLANS ARE | | | VERY DIFFICULT TO READ. PLEASE MAKE THEM MORE LEGIBLE. | | | | | | 3) THE ZONING AND LAND DEVELOPMENT REGULATIONS SPECIFY | | | THAT ANY SOURCE OF ILLUMINATION LOCATED WITHIN A | | | COMMERCIAL PLANNED DEVELOPMENT DISTRICT(WHICH IS | | | APPLIES TO BRANDSMART/BJS) SHALL NOT EXCEED ONE | | | FOOTCANDLE AT OR BEYOND THE BOUNDARIES OF SUCH | | | DEVELOPMENT. THE ONE FOOTCANDLE MAXIMUM IS EXCEEDED IN | | | A NUMBER OF LOCATIONS. THIS MUST BE CORRECTED. | | | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446. | | | [email protected] |
|