Plan Review Notes
Plan Review Notes For Permit 23050233
Permit Number 23050233
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-15 13:12:45THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
  
 1) ON THE LIFESAFETY PLAN KEY NOTES INDICATE ON #1
 EXISITING PATH OF TRAVEL BUT IN THE PROJECT DESCRIPTION
 STATES A REPLACEMENT OF PATH OF TRAVEL. PLEASE CLARIFIY
 WHICH IS CORRECT.
  
 2) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 3) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 4) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 5) DOOR SCHEDULE PAGE INDICATES THE REVOLVING DOORS
 CABIABLITY OF COLLAPSING BUT DOES NOT SHOW THE
 MEASUREMENTS OF THE TWO CREATED PARALLEL EGRESS PATHS
 BY THE COLLAPSING OF THE DOOR, PER NFPA 101 7.2.1.10
 REVOLVING DOOR ASSEMBLIES.
  
 6) PROVIDE THE DISTANCE BETWEEN THE SIDE DOOR AND THE
 REVOLVING DOOR MEETING NFPA 101 7.2.1.10 REVOLVING DOOR
 ASSEMBLIES.
  
 7.2.1.10.1 REVOLVING DOOR ASSEMBLIES, WHETHER USED OR
 NOT USED
 IN THE MEANS OF EGRESS, SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
 (1) REVOLVING DOOR WINGS SHALL BE CAPABLE OF BEING
 COLLAPSED
 INTO A BOOK-FOLD POSITION, UNLESS THEY ARE EXISTING
 REVOLVING
 DOORS APPROVED BY THE AUTHORITY HAVING JURISDICTION.
 (2) WHEN REVOLVING DOOR WINGS ARE COLLAPSED INTO THE
 BOOKFOLD
 POSITION, THE PARALLEL EGRESS PATHS FORMED SHALL
 PROVIDE
 AN AGGREGATE WIDTH OF 36 IN. (915 MM), UNLESS THEY
 ARE APPROVED EXISTING REVOLVING DOOR ASSEMBLIES.
 (3) REVOLVING DOOR ASSEMBLIES SHALL NOT BE USED WITHIN
 10 FT
 (3050 MM) OF THE FOOT OR THE TOP OF STAIRS OR
 ESCALATORS.
 (4) A DISPERSAL AREA ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION
 SHALL BE LOCATED BETWEEN STAIRS OR ESCALATORS AND
 THE REVOLVING DOOR ASSEMBLY.
 (5) THE REVOLUTIONS PER MINUTE (RPM) OF REVOLVING DOOR
 WINGS SHALL NOT EXCEED THE VALUES IN TABLE 7.2.1.10.1.
 (6) EACH REVOLVING DOOR ASSEMBLY SHALL HAVE A
 CONFORMING
 SIDE-HINGED SWINGING DOOR ASSEMBLY IN THE SAME WALL AS
 THE REVOLVING DOOR WITHIN 10 FT (3050 MM) OF THE
 REVOLVING
 DOOR, UNLESS ONE OF THE FOLLOWING CONDITIONS APPLIES:
 (A) REVOLVING DOOR ASSEMBLIES SHALL BE PERMITTED
 WITHOUT
 ADJACENT SWINGING DOOR ASSEMBLIES, AS REQUIRED BY
 7.2.1.10.1(6), IN STREET FLOOR ELEVATOR LOBBIES,
 PROVIDED
 THAT NO STAIRWAYS OR DOOR OPENINGS FROM OTHER
 PARTS OF THE BUILDING DISCHARGE THROUGH THE LOBBY AND
 THE LOBBY HAS NO OCCUPANCY OTHER THAN AS A MEANS OF
 TRAVEL BETWEEN THE ELEVATORS AND STREET.
 (B) THE REQUIREMENT OF 7.2.1.10.1(6) SHALL NOT APPLY TO
 EXISTING REVOLVING DOOR ASSEMBLIES WHERE THE NUMBER
 OF REVOLVING DOOR ASSEMBLIES DOES NOT EXCEED THE
 NUMBER OF SWINGING DOOR ASSEMBLIES WITHIN 20 FT
 (6100 MM) OF THE REVOLVING DOOR ASSEMBLY.
 7.2.1.10.2 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 REVOLVING
 DOOR ASSEMBLIES SHALL BE PERMITTED AS A COMPONENT IN
 A MEANS OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA
 ARE MET:
 (1) REVOLVING DOOR OPENINGS SHALL NOT BE GIVEN CREDIT
 FOR
 MORE THAN 50 PERCENT OF THE REQUIRED EGRESS CAPACITY.
 (2) EACH REVOLVING DOOR OPENING SHALL NOT BE CREDITED
 WITH
 MORE THAN A 50-PERSON CAPACITY OR, IF OF NOT LESS THAN
 A 9 FT
 (2745 MM) DIAMETER, A REVOLVING DOOR ASSEMBLY SHALL BE
 PERMITTED EGRESS CAPACITY BASED ON THE CLEAR OPENING
 WIDTH PROVIDED WHEN COLLAPSED INTO A BOOK-FOLD
 POSITION.
 (3) REVOLVING DOOR WINGS SHALL BE CAPABLE OF BEING
 COLLAPSED
 INTO A BOOK-FOLD POSITION WHEN A FORCE NOT EXCEEDING
 130 LBF
 (580 N) IS APPLIED TO THE WINGS WITHIN 3 IN. (75 MM) OF
 THE
 OUTER EDGE.
 7.2.1.10.3 REVOLVING DOOR ASSEMBLIES NOT USED AS A
 COMPONENT
 OF A MEANS OF EGRESS SHALL HAVE A COLLAPSING FORCE NOT
 EXCEEDING 180 LBF (800 N) APPLIED AT A POINT 3 IN. (75
 MM)
 FROM THE OUTER EDGE OF THE OUTER WING STILE AND 40 IN.
 (1015 MM) ABOVE THE FLOOR.
 7.2.1.10.4 THE REQUIREMENT OF 7.2.1.10.3 SHALL NOT
 APPLY TO
 REVOLVING DOOR ASSEMBLIES, PROVIDED THAT THE COLLAPSING
 FORCE
 IS REDUCED TO A FORCE NOT TO EXCEED 130 LBF (580 N)
 UNDER ALL OF
 THE FOLLOWING CONDITIONS:
 (1) POWER FAILURE, OR REMOVAL OF POWER TO THE DEVICE
 HOLDING
 THE WINGS IN POSITION
 (2) ACTUATION OF THE AUTOMATIC SPRINKLER SYSTEM, WHERE
 SUCH A
 SYSTEM IS PROVIDED
 (3) ACTUATION OF A SMOKE DETECTION SYSTEM THAT IS
 INSTALLED TO
 PROVIDE COVERAGE IN ALL AREAS WITHIN THE BUILDING THAT
 ARE
 WITHIN 75 FT (23 M) OF THE REVOLVING DOOR ASSEMBLIES
 (4) ACTUATION OF A CLEARLY IDENTIFIED MANUAL CONTROL
 SWITCH IN
 AN APPROVED LOCATION THAT REDUCES THE
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561.804.4728
 [email protected]
  