| 2023-05-11 12:14:26 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23050166 | | | 5/11/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET L2.0: THE DRAWING APPEARS TO BE INCOMPLETE. | | | THERE ARE 5 INTERIOR PIPE LOCATIONS THAT ARE LABELED AS | | | SOURCE PIPE, HOWEVER THE DRAWING DOESN???T SHOW THE | | | ACTUAL WATER SOURCE FOR THE IRRIGATION SYSTEM AS | | | REQUIRED- SEC. 107.2.1 WPB. PLEASE NOTE IF CONNECTING | | | TO EXISTING POTABLE WATER PIPES IN THE BUILDING EACH | | | CONNECTION POINT WILL REQUIRE INSTALLATION A BACKFLOW | | | PREVENTER PER SEC. 608.17.5 FBC P. IF THERE IS ONE MAIN | | | SOURCE PIPE CONNECTING TO THE CITY WATER SERVICE (CWS) | | | THE BF PREVENTER SHALL BE AT THE POINT OF CONNECTION | | | AND WILL REQUIRE A SEPARATE PERMIT- SEC. 107.2.1 WPB & | | | SEC. E WPB CROSS-CONNECTION MANUAL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|