| 2023-06-30 16:23:09 | RE-ROOF THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23050036 |
| | 2206 MERCER AVE |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE FASTENER WITHDRAWAL RESISTANCE TEST TAS 105 |
| | (SIGNED AND SEALED) AS REQUIRED BY LIMITATION #5.6.1. |
| | AND NOTE #11 OF PRODUCT APPROVAL FL14083-R28 SUBMITTED. |
| | FAC 61G20.3.001. |
| | |
| | RESPONSE: |
| | DIGITAL SIGNATURE COMMENTS: |
| | A)TESTING REPORT HAS A COPY OF THE ENGINEER???S DIGITAL |
| | SIGNATURE. DIGITAL SIGNATURES ARE NOT ALLOWED TO BE |
| | PRINTED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER |
| | NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE |
| | OF THE ENGINEER AS REQUIRED BY SEC. 61G15-23.004 FAC |
| | AND CHAPTER 471 F.S. |
| | |
| | B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | ENGINEERS |
| | 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING |
| | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3- SIGNATURE ON ENGINEER ROOF COVERINGS ATTACHMENT |
| | CALCULATIONS: |
| | A)CALCULATIONS HAVE A COPY OF THE ENGINEER'S SIGNATURE |
| | AND SEAL. NEED ORIGINAL SEAL/SIGNATURE WHEN SUBMITTED |
| | FOR PUBLIC RECORDS. SEC. 471 F.S. |
| | NOTE: ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | RESPONSE: |
| | DIGITAL SIGNATURE COMMENTS: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | ENGINEERS |
| | 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING |
| | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |