| 2023-07-03 09:17:16 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-23050026 |
| | 7/3/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: THE 2-INCH FIXTURE BRANCH/STACK FOR THE |
| | TWO WASHING MACHINE FIXTURE DRAINS SHALL BE INCREASED |
| | TO 3-INCH IN COMPLIANCE WITH SEC. 406.2 FBC P. |
| | |
| | 2) A-2: PLEASE PROVIDE THE FOLLOWING LIST OF FBC |
| | ACCESSIBILITY COMPLIANCE DETAILS. |
| | A) TURNING CIRCLE DIAMETER MEASUREMENT. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WASHING MACHINES AND DRYERS- SEC. 611.2. |
| | C) PROVIDE AN ELEVATION DETAIL FOR THE WASHING MACHINES |
| | SHOWING DOOR OPENING HEIGHTS- SEC. 611.4. |
| | |
| | 3) A-2: THE FLOOR PLAN SHOWS A RECTANGULAR DIAGRAM BY |
| | THE LAUNDRY SINK. IS THE INTENTION TO SHOW A CLEAR |
| | FLOOR SPACE FOR THE FIXTURE? PLEASE NOTE A CLEAR FLOOR |
| | SPACE FOR A FORWARD APPROACH SHALL BE 30X48 INCHES AND |
| | SHALL EXTEND BELOW THE SINK AND INCLUDE KNEE AND TOE |
| | CLEARANCES- SEE SECS. 606.2 & 306. ACCESSIBLE SINKS |
| | SHALL ALSO BE MOUNTED MAXIMUM 34-INCHES FROM THE |
| | FINISHED FLOOR MEASURED TO THE FRONT OF THE RIM OF THE |
| | SINK- 606.3. PLEASE PROVIDE DETAILS TO SHOW COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |