Plan Review Notes
Plan Review Notes For Permit 23050025
Permit Number 23050025
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-30 16:10:591ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050025
 6/30/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-5: PLEASE REFER TO SEC. 810.1 FBC EX AND
 PROVIDE THE EXISTING OCCUPANT LOAD OF THE FLOOR AND THE
 INCREASED OCCUPANT LOAD BASED ON THE OFFICE CONVERSION
 TO NEW CLASSROOM. PLEASE NOTE IF THE EXISTING LOAD
 INCREASES BY MORE THAN 20%, PLUMBING FIXTURES SHALL BE
 PROVIDED IN COMPLIANCE WITH TABLE 403.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  