| 2023-06-21 14:12:43 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE DETAIL ALL TREATMENT ROOM RECEPTACLES TO |
| | COMPLY WITH THE FOLLOWING: |
| | 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL |
| | EQUIPMENT IN PATIENT CARE SPACES |
| | (A) WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT |
| | CARE SPACES SHALL BE PROVIDED WITH AN EFFECTIVE |
| | GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL |
| | RACEWAY SYSTEM OR A CABLE HAVING A METALLIC ARMOR OR |
| | SHEATH ASSEMBLY |
| | |
| | 2) PLEASE DETAIL ANY RECEPTACLES WITHIN 6 FEET OF ANY |
| | SINK AS BEING GFI PROTECTED IN ACCORDANCE WITH NEC |
| | 210.8 (B)(5). THIS SHOULD INCLUDE RECEPTACLES WITHIN 6 |
| | FEET OF TREATMENT ROOM SINKS |
| | |
| | 3) PLEASE DETAIL ANY APPLICABLE RECEPTACLES ARE TAMPER |
| | RESISTANT IN ACCORDANCE WITH NEC 406.12 |
| | |
| | 4) PLEASE PROVIDE A NOTE STATING ALL LOW VOLTAGE WIRING |
| | INCLUDING BUT NOT LIMITED TO VOICE, DATA, FIRE ALARM, |
| | ACCESS CONTROL, SECURITY AND SIGNS REQUIRE A SEPARATE |
| | PERMIT |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |