| Plan Review Notes For Permit 23041470 |
| Permit Number |
23041470 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-04 09:54:22 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-4; | | | EXPOSURE (C); ENCLOSURE (OPEN); ROOF HEIGHT H<15; | | | ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT | | | ENCLOSURE FOR THE LISTED ADDRESS IS ENCLOSED; WIND | | | SPEED 170. PLEASE SELECT THE CORRECT OPTIONS INCLUDING | | | CORRECT FASTENING PATTERNS FOR ZONE 1 PRIME, ZONES 1, 2 | | | & 3. IF APPLICABLE. | | | 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF | | | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN | | | ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE | | | DRAINAGE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|