| 2023-07-19 14:05:14 | RESIDENTIAL (R3) FOUNDATION BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23041442 |
| | 3140 WASHINGTON RD |
| | |
| | (1)-THE PROPOSED ALTERATION/ADDITION IS GOING TO BE |
| | BUILT IN A AE FLOOD ZONE WITH A BASE FLOOD ELEVATION |
| | (BFE) OF 6, 7 AND 8 FEET BASED ON NAVD 88. |
| | THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL |
| | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL |
| | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR |
| | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. |
| | NOTE: PLANS (INCLUDING THE FOUNDATION PLAN) NEED TO |
| | SHOW THE PROPOSED FINISHED FLOOR ELEVATIONS FOR MAIN |
| | HOUSE AND GARAGES. ALSO, NEED TO PROVIDE THE |
| | CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY |
| | SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW. |
| | CITY ORDINANCE 4729-17. |
| | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| | CODE. |
| | SEC. 107.3.5.3 CITY AMENDMENTS. |
| | |
| | DURING THE CONSTRUCTION OF THIS STRUCTURE THREE |
| | DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE |
| | REQUIRED: |
| | (A)CONSTRUCTION DRAWINGS. |
| | (B)BUILDING UNDER CONSTRUCTION. |
| | (C)FINISHED CONSTRUCTION. |
| | |
| | (2)- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| | DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| | WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| | 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | COORDINATE WITH ITEM #1 ABOVE TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | (3)STRUCTURAL PLANS ARE INCOMPLETE: |
| | (A) THEY DON'T SHOW THE PROPOSED ADDITION. ONLY |
| | EXISTING HOUSE IS PROVIDED. PROVIDE COMPLETE PLANS AND |
| | SHOW FINISH FLOOR ELEVATIONS. COORDINATE WITH ITEM #1 |
| | ABOVE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | (B)DESIGN CRITERIA ON SHEET S100: ENGINEER TO SPECIFY |
| | THE WIND SPEED CONVERSION. SEC. R301.2.1.3 |
| | FBC-RESIDENTIAL. |
| | |
| | (3)SEPARATE PERMIT REQUIRED FOR DEMOLITION OF CABANA, |
| | EXTERIOR WALLS OF MAIN HOUSE, POOL & DECK. SEC. 105.1 |
| | CITY AMENDMENTS. |
| | |
| | (4) DIGITAL SIGNATURE REVIEW. |
| | (A)GEOTECHNICAL REPORT: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | (B)PLUMBING PLANS SUBMITTED: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | (C)ELECTRICAL PLAN E1.1 SUBMITTED: |
| | ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |