Plan Review Notes For Permit 23041353
Permit Number 23041353
Review Stop M
Sequence Number 1
Notes
Date Text
2023-05-11 16:39:411ST REVIEW FMC
 PERMIT: 23041353
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXISTING HP-2 WAS A 4-TON ON THE PREVIOUS DRAWING,
 IT IS NOW A 5-TON.
 EXISTING HP-3 WAS A1.5 TON ON THE PREVIOUS DRAWING, IT
 IS NOW A 4-TON. PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THESE CHANGES. FEC C403.2.1
  
 2) IT APPEARS THE DUCT WORK FOR AHU-8 HAS BEEN
 REROUTED. WHAT IS THIS MDF CLOSET AND WHY DOES IT NOT
 NEED OUTDOOR AIR? FMC 403.3.1.1
  
 3) PROVIDE THE AIRFLOW FOR THE HP-8.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER