| 2023-05-11 16:39:41 | 1ST REVIEW FMC | | | PERMIT: 23041353 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) EXISTING HP-2 WAS A 4-TON ON THE PREVIOUS DRAWING, | | | IT IS NOW A 5-TON. | | | EXISTING HP-3 WAS A1.5 TON ON THE PREVIOUS DRAWING, IT | | | IS NOW A 4-TON. PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THESE CHANGES. FEC C403.2.1 | | | | | | 2) IT APPEARS THE DUCT WORK FOR AHU-8 HAS BEEN | | | REROUTED. WHAT IS THIS MDF CLOSET AND WHY DOES IT NOT | | | NEED OUTDOOR AIR? FMC 403.3.1.1 | | | | | | 3) PROVIDE THE AIRFLOW FOR THE HP-8. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|