| 2023-04-27 09:29:29 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | ENGINEER???S LETTER NOT PROPERLY SEALED. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16730-R41 |
| | IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM |
| | BEACH IS NOT LOCATED IN A HVHZ. PROVIDE A COMPLETE SET |
| | OF 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE |
| | PROPOSED FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER |
| | PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS |
| | FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34 |
| | HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A |
| | COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS |
| | MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE |
| | UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE |
| | SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS |
| | FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A |
| | DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS |
| | OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF |
| | APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. |
| | 4. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| | APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| | PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| | SUBMITTING. REVIEW STAMP WITH INITIALS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |