2023-05-03 11:55:281ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23041317
 5/3/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER DRAWING IS INCOMPLETE BECAUSE IT DOES
 NOT INCLUDE THE PIPING AND APPLIANCES INSTALLED UNDER
 PERMIT 13040130. A COMPLETE RISER IS REQUIRED PER SECS.
 G2412.3 & G2412.4 FBC RES. REVISE THE RISER TO SHOW THE
 BRANCH PIPING CONNECTIONS TO THE EXISTING WATER HEATER
 AND TO THE INTERIOR APPLIANCES.
  
 A) PLEASE REVISE THE GAS NOTES TO SHOW THE LONGEST
 LENGTH AND THE TOTAL BTU'S BASED ON THE REVISED RISER.
  
 2) THE LICENSED CONTRACTOR ROBERT NAVARRO SHALL PROVIDE
 HIS SIGNATURE ON THE REVISED RISER DRAWING- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER