| Date |
Text |
| 2023-05-23 09:53:25 | INSUFFICIENT |
| | |
| | 1) ACACIA ROAD AND CURRIE CRESCENT AT THE LOCATION OF |
| | THE PROPOSED POLE IS CURRENTLY UNDER RECONSTRUCTION/HAS |
| | RECENTLY BEEN RECONSTRUCTED WHICH MAY REQUIRE THAT THE |
| | POLE AND UNDERGROUND ELECTRIC TO THE POLE BE RELOCATED. |
| | THE WORK INCLUDES BOTH ABOVE AND BELOW GROUND |
| | INFRASTRUCTURE, TO INCLUDE THE REMOVAL OF SOME OF THE |
| | UTILITY POLES. PLEASE CONTACT LINDA QUINONES, SENIOR |
| | ENGINEERING PROJECT COORDINATOR, AT 561-494-1085 FOR A |
| | COPY OF THE LATEST PLANS. THE ENGINEERING PLANS AND |
| | SURVEY NEED TO BE UPDATED ACCORDINGLY TO SHOW ACCURATE |
| | PLANS BASED ON THE RECONSTRUCTION OF THE ACACIA ROAD |
| | AND CURRIE CRESCENT RIGHTS-OF-WAY. |
| | |
| | 2) BASED ON THE FINAL RECONSTRUCTION PLANS, THE POLE |
| | WILL NEED TO BE LOCATED TO ALIGN WITH THE EXISTING AND |
| | PROPOSED TREES AND POLES IN THE RIGHT-OF-WAY. |
| | |
| | 3) ALL UNDERGROUND UTILITIES AND FEATURES NEED TO BE |
| | PROVIDED ON THE SURVEY. THE PROVIDED SURVEY |
| | SPECIFICALLY STATES THAT NO UNDERGROUND UTILITY LOCATES |
| | WERE DONE, WHICH DOES NOT COMPLY WITH THE CITY CODE |
| | REQUIREMENTS. |
| | |
| | 4) THE CROSS SECTION SHOWS THAT THERE IS A CLEAR ZONE |
| | OF 2.5 FEET, WHICH DOES NOT COMPLY WITH THE ADA MINIMUM |
| | REQUIREMENT OF 36 INCHES. |
| | |
| | 5) PROVIDE ELEVATION DETAILING THE HEIGHT, AND DIAMETER |
| | OF THE PROPOSED POLE. THE POLE COLOR AT THIS LOCATION |
| | SHALL BE RAL/RAYCAP 7042 TRAFFIC GREY A OR EQUIVALENT. |
| | THIS SHALL BE SPECIFICALLY STATED ON THE PLANS. |
| | |
| | 6) A UTILITY POWER PLAN THAT SHOWS HOW THE UNDERGROUND |
| | POWER IS BEING PROVIDED TO THE POLE, INCLUDING THE |
| | POWER SOURCE, WAS NOT INCLUDED. THE UNDERGROUND POWER |
| | PATH, INCLUDING ANY BORE PITS AND HANDHOLES ARE |
| | REQUIRED TO BE SHOWN ON THE WIRELESS COMMUNICATION |
| | FACILITY ROW PERMIT APPLICATION. |
| | |
| | 7) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC |
| | BORE FOR THE FULL LENGTH OF THE INSTALLATION. THE |
| | UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE |
| | UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER, |
| | SANITARY, ELECTRIC, AND CABLE) AND ANY TREE ROOT |
| | SYSTEMS. |
| | |
| | |
| | REVIEWED BY: |
| | GAISHA (ANNE) VOLCY |
| | [email protected] |