| 2023-07-19 13:47:36 | NFIP COMMENTS: |
| | |
| | (1)-THE PROPOSED ALTERATION/ADDITION IS GOING TO BE |
| | BUILT IN A AE FLOOD ZONE WITH A BASE FLOOD ELEVATION |
| | (BFE) OF 6, 7 AND 8 FEET BASED ON NAVD 88. |
| | THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL |
| | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL |
| | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR |
| | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. |
| | NOTE: PLANS (INCLUDING THE FOUNDATION PLAN) NEED TO |
| | SHOW THE PROPOSED FINISHED FLOOR ELEVATIONS FOR MAIN |
| | HOUSE AND GARAGES. ALSO, NEED TO PROVIDE THE |
| | CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY |
| | SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW. |
| | CITY ORDINANCE 4729-17. |
| | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| | CODE. |
| | SEC. 107.3.5.3 CITY AMENDMENTS. |
| | |
| | DURING THE CONSTRUCTION OF THIS STRUCTURE THREE |
| | DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE |
| | REQUIRED: |
| | (A)CONSTRUCTION DRAWINGS. |
| | (B)BUILDING UNDER CONSTRUCTION. |
| | (C)FINISHED CONSTRUCTION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |