2023-07-19 13:40:03RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041293
 3140 WASHINGTON RD
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 (1)-THE PROPOSED ALTERATION/ADDITION IS GOING TO BE
 BUILT IN A AE FLOOD ZONE WITH A BASE FLOOD ELEVATION
 (BFE) OF 6, 7 AND 8 FEET BASED ON NAVD 88.
 THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 NOTE: PLANS (INCLUDING THE FOUNDATION PLAN) NEED TO
 SHOW THE PROPOSED FINISHED FLOOR ELEVATIONS FOR MAIN
 HOUSE AND GARAGES. ALSO, NEED TO PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY
 SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW.
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE CONSTRUCTION OF THIS STRUCTURE THREE
 DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED:
 (A)CONSTRUCTION DRAWINGS.
 (B)BUILDING UNDER CONSTRUCTION.
 (C)FINISHED CONSTRUCTION.
  
 (2)- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
 COORDINATE WITH ITEM #1 ABOVE TO AVOID
 CONFLICTS/DELAYS.
  
 (3)STRUCTURAL PLANS ARE INCOMPLETE:
 (A) THEY DON'T SHOW THE PROPOSED ADDITION. ONLY
 EXISTING HOUSE IS PROVIDED. PROVIDE COMPLETE PLANS AND
 SHOW FINISH FLOOR ELEVATIONS. COORDINATE WITH ITEM #1
 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (B)DESIGN CRITERIA ON SHEET S100: ENGINEER TO SPECIFY
 THE WIND SPEED CONVERSION. SEC. R301.2.1.3
 FBC-RESIDENTIAL.
  
 (C)ENGINEER TO SPECIFY THE COMPONENTS AND CLADDING
 DESIGN PRESSURES FOR DOORS, WINDOWS, ROOFING COVERINGS,
 ETC.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (D)PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS
 SHOWING COMPLIANCE WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. SPECIFY NAIL TYPE, SIZE AND SPACING.
 NOTE: NEED TO USE RING SHANK NAILS. ROOF SHEATHING
 NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
  
 (4)PROVIDE COMPLETE SET OF PLANS INCLUDING WALL,
 SECTIONS, ALL EXTERIOR ELEVATIONS, ETC. SEC. 107.2.1
 CITY AMENDMENTS. SEC. 107.3.5.3 CITY AMENDMENTS.
  
 (5)PROVIDE COMPLETE FLOOR PLANS SHOWING THE DIMENSIONS
 OF ALL ROOMS. R304.2 FBC-RESIDENTIAL.
  
 (6) SPECIFY HOW PROVIDING HEAT TO THE PROPOSED
 ALTERATION AND ADDITION. PROVIDE MECHANICAL FLOR PLANS
 AND SPECIFICATIONS. SEC. R303.10 FBC-RESIDENTIAL.
  
 (7)CLEARLY SPECIFY THE SECOND FLOOR LIVE AND DEAD
 LOADS. SEC. R301.1 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND PLANTER AREA ON PROPOSED SECOND
 FLOOR PLAN TO AVOID CONFLICTS/DELAYS.
  
 (8) ROOF LIVE AND DEAD LOADS.
 CLEARLY SPECIFY THE TOP CHORD LIVE AND DEAD LOADS AND
 BOTTOM CHORD LIVE AND DEAD LOADS. SEC. R301.1
 FBC-RESIDENTIAL AND TABLE R301.5 FBC-RESIDENTIAL.
  
 (9)PROVIDE COMPLETE WINDOW AND DOOR SCHEDULES.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 (10)WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 (11)PLANS DON'T PROVIDE SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 (12)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING TERRACE GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN DESIGNER OF
 RECORD NEEDS TO SPECIFY THE DESIGN GUIDELINES REQUIRED
 BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 AND
 CLEARLY SPECIFY ON PLANS THAT SHOP DRAWINGS NEED TO BE
 SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION. ALL SHOP
 DRAWINGS TO BE REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 (13)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION: DIMENSIONS, RISERS, TREADS,
 HANDRAILS, GUARDRAILS, ETC. SHOWING COMPLIANCE WITH
 SEC. R311.7 FBC-RESIDENTIAL.
  
 (14) NEED TO SPECIFY HANDRAILS BY ENTRY PORCH STAIRS AS
 REQUIRED BY SEC. R311.7.8 FBC-RESIDENTIAL.
  
 (15)SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS (NEW AND EXISTING) AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 (16)NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 (17)PROVIDE DETAILS/SPECIFICATIONS FOR FIREBLOCKING,
 INCLUDING STAIRWAYS AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 (18)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 (19)SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1
 FBC-RESIDENTIAL.
  
 (20)PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING
 SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 (21)PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 (22)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 WALL FLASHING AT ALL EXTERIOR OPENINGS. SEC. R703.4
 FBC-RESIDENTIAL.
  
 (23)PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
 (A)EXTERIOR DOORS AS SHOWN ON PLANS. (NOTE: PLEASE
 IDENTIFY EACH PRODUCT APPROVAL. FOR EXAMPLE ENTRY DOOR,
 GARAGE SWING DOOR, ETC.)
 (B)WINDOWS AS SHOWN ON PLANS.
 (C)WINDOWS AND DOORS MULLIONS (NOTE: NEED TO SPECIFY
 MULLION SIZE TO VERIFY PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL).
 (D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 (E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 (F)ROOF TILE. AND CLEARLY SPECIFY/MARK FASTENING
 METHOD.
 (G)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 (H)HIP & RIDGE METAL SUPPORT TO BE USED.
 (I)SECOND FLOOR DECK UNDERLAYMENT FOR FLOOR FINISH
 SPECIFIED ON PLANS.
 (J)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
 (K)FOOD VENTS IF SPECIFIED ON PLANS.
  
 (24)DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 (25)SEPARATE PERMIT REQUIRED FOR DEMOLITION OF CABANA,
 EXTERIOR WALLS OF MAIN HOUSE, POOL & DECK. SEC. 105.1
 CITY AMENDMENTS.
  
 (26)VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE PROPOSED SCOPE OF WORK. VALUATION
 TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD
 AND PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE
 ALL COSTS. PROVIDE COMPLETE COST BREAKDOWN INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 (27) DIGITAL SIGNATURE REVIEW.
 (A)GEOTECHNICAL REPORT:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (B)PLUMBING PLANS SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (C)ELECTRICAL PLAN E1.1 SUBMITTED:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 (28)NEED ENERGY CALCULATIONS. SEC. 1106 FBC-EXISTING
 BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER