| 2023-07-05 13:25:45 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ROOMS LABELED WORKROOM A, B AND BACK BAR APPEAR TO |
| | BE CLASSIFIED AS A KITCHEN IN ACCORDANCE WITH NEC 100 |
| | DEFINITIONS. EQUIPMENT DETAILED ON KITCHEN EQUIPMENT |
| | SCHEDULE DETAIL THEY ARE TO TERMINATE TO RECEPTACLES |
| | WHICH ARE REQUIRED TO BE GFIC PROTECTED IN ACCORDANCE |
| | WITH NEC 210.8. PLEASE CORRECT PLANS TO INDICATE ALL |
| | RECEPTACLES LOCATED IN THESE KITCHEN AREAS COMPLY WITH |
| | NEC 210.8 |
| | |
| | NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL |
| | (B) OTHER THAN DWELLING UNITS. |
| | ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND |
| | OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES |
| | RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS |
| | INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | (2) KITCHENS |
| | |
| | NEC 100 DEFINITIONS |
| | KITCHEN. |
| | AN AREA WITH A SINK AND PERMANENT PROVISIONS FOR FOOD |
| | PREPARATION AND COOKING |
| | |
| | 3) SHEET E202 REFERS, INCORRECTLY TO A DETAIL ON SHEET |
| | E 301 DETAIL 7 THAT APPEARS TO BE SHOWN ON SHEET E 302 |
| | DETAIL 7. PLEASE CORRECT AS APPLICABLE. FBC 107.2 |
| | |
| | 4) SHEET E 303 DETAIL 2, BANQUET CLOSTER INDICATES A |
| | DIMMED DUPLEX RECEPTACLE. NEC 404.14 STATES GENERAL USE |
| | DIMMER SWITCHES SHALL ONLY BE USED TO CONTROL PERMANTLY |
| | INSTALLED LUMINAIRES. PLEASE CORRECT AS APPLICABLE. |
| | |
| | NEC 404.14 RATING AND USE OF SWITCHES. |
| | (E) DIMMER SWITCHES. |
| | GENERAL-USE DIMMER SWITCHES SHALL BE USED ONLY TO |
| | CONTROL PERMANENTLY INSTALLED INCANDESCENT LUMINAIRES |
| | UNLESS LISTED FOR THE CONTROL OF OTHER LOADS AND |
| | INSTALLED ACCORDINGLY. |
| | |
| | 5) PLEASE INDICATE TAMPER RESISTANT RECEPTACLES IN ALL |
| | APPLICABLE LOCATIONS, IN ACCORDANCE WITH NEC 406.12(6) |
| | REFERRED TO IN 518.2 ASSEMBLY AREAS. |
| | |
| | 406.12 TAMPER-RESISTANT RECEPTACLES. |
| | ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| | NONLOCKING-TYPE RECEPTACLES IN THE AREAS SPECIFIED IN |
| | 406.12(1) THROUGH (7) SHALL BE LISTED TAMPER-RESISTANT |
| | RECEPTACLES. |
| | (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| | TO INCLUDE PLACES OF WAITING TRANSPORTATION, |
| | GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS |
| | |
| | 2) PLEASE PROVIDE A NOTE STATING SIGNS AND ALL LOW |
| | VOLTAGE WIRING INCLUDING BUT NOT LIMITED TO, VOICE, |
| | DATA, AUDIO, VIDEO, SECURITY, ACCESS, POS, FIRE ALARM, |
| | ETC. REQUIRE A SEPARATE PERMIT. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |