Plan Review Notes For Permit 23041232
Permit Number 23041232
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2023-05-02 09:44:20SIGNATURE REVIEW FAILED
 1) PLANS AND DRAWINGS SUBMITTED DO NOT CONTAIN THE
 REQUIRED SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. WEST PALM BEACH AMENDMENT 107.2
  
 WPBA 107.2 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) PLANS OR DRAWINGS CONTAINING AN ENGINEERS DIGITAL
 SIGNATURE CANNOT BE CERTIFIED USING BLUEBEAM OR ADOBE
 SOFTWARE.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE CORRECT AS APPLICABLE
  
 PLEASE SUBMIT DIGITALLY SEALED OR SIGNED PLANS AS
 OUTLINED ABOVE FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  