Plan Review Notes
Plan Review Notes For Permit 23041217
Permit Number 23041217
Review Stop G
Sequence Number 1
Notes
Date Text
2023-04-26 09:25:281ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23041217
 4/26/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-2 GAS RISER: THE GAS RISER DRAWING IS
 INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE PIPING TO
 THE NEW RANGE AND THE EXISTING GAS WATER HEATER- SECS.
 G2412.3 & G2412.4 FBC RES. IF THE POOL HEATER IS A NEW
 AND NOT A REPLACEMENT, IT SHALL BE INSTALLED UNDER A
 SEPARATE GAS PERMIT AND PLUMBING SUB-PERMIT- SEC. 105.1
 & 107.2.1 WPB.
 THE REVISED GAS RISER SHALL PROVIDE THE FOLLOWING
 ITEMS-
 A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 B) TYPES AND SIZES OF PIPING.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  