2023-05-17 11:30:06RESIDENTIAL(R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23041216
 811 HOLLYWOOD PL
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R8:
 SELECTED ASSEMBLY W-156 CANNOT BE USED BECAUSE IT
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 THE MAXIMUM DESIGN PRESSURES OF BONDED ASSEMBLIES
 CANNOT BE INCREASED. SEE LIMITATION #5.7.3 OF PRODUCT
 APPROVAL SUBMITTED.
 NEED TO SELECT ANOTHER BONDED ASSEMBLY THAT MEETS OR
 EXCEEDS THE DESIGN PRESSURES FOR ALL ROOF ZONES OR
 SELECT MECHANICALLY ATTACHED ASSEMBLY THAT ALLOWS NAIL
 ENHANCEMENT RAS 117 CALCULATIONS SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,