| Notes |
| Date |
Text |
| 2023-05-02 14:07:54 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IN SECTION II, THE ENGINEER'S CALCULATIONS FOR THE | | | NUMBER OF FASTENERS FOR ZONE 2 ARE INCORRECT. THE | | | CALCULATION HAS 20.86447 FASTENERS THIS SHOULD BE | | | ROUNDED UP TO 21 FASTENERS AND 20 ARE SPECIFIED. PLEASE | | | CORRECT. | | | | | | 2) IN SECTION II, THE ENGINEER'S CALCULATIONS FOR THE | | | NUMBER OF FASTENERS FOR ZONE 3 ARE INCORRECT. THE | | | CALCULATION HAS 28.60073 FASTENERS THIS SHOULD BE | | | ROUNDED UP TO 29 FASTENERS AND 28 ARE SPECIFIED. PLEASE | | | CORRECT. | | | | | | 3) THE PROJECT ADDRESS ON THE CALCULATIONS IS NOT | | | CORRECT. THE NAME OF THE ROAD IS SPELLED WRONG. IT | | | SHOULD BE OKEECHOBEE ROAD. PLEASE CORRECT. |
|