2023-05-02 14:07:54PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN SECTION II, THE ENGINEER'S CALCULATIONS FOR THE
 NUMBER OF FASTENERS FOR ZONE 2 ARE INCORRECT. THE
 CALCULATION HAS 20.86447 FASTENERS THIS SHOULD BE
 ROUNDED UP TO 21 FASTENERS AND 20 ARE SPECIFIED. PLEASE
 CORRECT.
  
 2) IN SECTION II, THE ENGINEER'S CALCULATIONS FOR THE
 NUMBER OF FASTENERS FOR ZONE 3 ARE INCORRECT. THE
 CALCULATION HAS 28.60073 FASTENERS THIS SHOULD BE
 ROUNDED UP TO 29 FASTENERS AND 28 ARE SPECIFIED. PLEASE
 CORRECT.
  
 3) THE PROJECT ADDRESS ON THE CALCULATIONS IS NOT
 CORRECT. THE NAME OF THE ROAD IS SPELLED WRONG. IT
 SHOULD BE OKEECHOBEE ROAD. PLEASE CORRECT.