| 2023-05-02 15:37:58 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23041206 |
| | 5/2/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET PG-1: PLEASE DO NOT USE THE PHRASE (EITHER OR) |
| | CONCERNING THE TYPE OF GAS PIPING TO BE INSTALLED. EACH |
| | TYPE OF PIPING HAS LIMITIATIONS OF USE. IDENTIFY OR |
| | LABEL EACH SEGMENT OF PIPING SHOWN ON THE PLAN AND IN |
| | THE RISER DRAWING- SECS. G2414.4 & G2414.6 FBC RES. |
| | PLEASE NOTE UNPROTECTED STEEL PIPE SHALL NOT BE RUN |
| | UNDERGROUND, AND PE PIPING SHALL NOT BE RUN UNDER ANY |
| | BUILDING OR SLAB- SECS. G2415.11 & G2415.17.1. |
| | |
| | 2) PG-1: BASED ON THE SCHEDULE 40 METALLIC LOW PRESSURE |
| | PIPE SIZING TABLE IN THE FBC RES- TABLES G2413.4(1) THE |
| | ??-INCH PIPE SUPPLYING THE WATER HEATER SHALL BE |
| | INCREASED TO 1-INCH. |
| | |
| | 3) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE- SEC. G2407.1 FBC RES. IF USING THE STANDARD |
| | INDOOR AIR METHOD THE MINIMUM REQUIRED VOLUME SHALL 50 |
| | CU.FT. PER 1000 BTU OF THE RANGE INPUT RATING- SEC. |
| | G2407.5 FBC RES. |
| | |
| | 4) PG-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | DRYER- SEC. G2407.1 FBC RES. PLEASE NOTE THE EXCEPTION |
| | WHICH ALLOWS FOR MAKEUP AIR TO BE SUBSTITUTED IN |
| | ACCORDANCE WITH SEC. G2439.5. |
| | |
| | 5) PG-1: SHOW A MINIMUM 4 FT. CLEARANCE FOR THE WATER |
| | HEATER EXHAUST TO THE WINDOWS AND DOORS- SECS. G2427.8 |
| | & G2448.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |